The XSSR-TH series is a DIN rail mounted integrated AC solid state relay designed for compact control cabinets and industrial automation systems. Combining a solid state relay and high-efficiency heat sink into a slim module, it offers reliable switching performance, excellent thermal management, and convenient installation. Featuring opto-isolated input, built-in protection circuitry, LED status indication, and zero-cross or random triggering options, the XSSR-TH is ideal for temperature control equipment, HVAC systems, industrial heaters, packaging machinery, and automation control applications.
Load Voltage: 24–480VAC
Control Voltage: 3–32VDC or 80–250VAC
Rated Load Current: 5A–25A


Available with zero-cross and random turn-on options to suit different AC load control applications.

Offers clear visual indication of operating status for easier monitoring and troubleshooting.

Provides safe electrical isolation between control and load circuits while improving system noise immunity.

Integrated protection circuitry enhances reliability and improves resistance to electrical interference.

Built-in aluminum heat sink provides efficient thermal management for stable long-term operation.

Compact DIN rail mounting structure saves cabinet space and simplifies installation.
Product model | XSSR-DA□□TH | XSSR-AA□□TH |
| Control voltage | 3-32 VDC | 80-250VAC |
| Control current | ≤25mA | ≤25mA |
| Reverse voltage | 32VDC | / |
| Guarantee close voltage | 1VDC | 30VAC |
| Guarantee open voltage | 3VDC | 80VAC |
| Load voltage | 24-480VAC | |
| Load max current | 5A-25A | |
| Load mini current | 0.08A | |
| Breakover voltage | ≤2VAC | |
| Output leakage current | ≤5mA | |
| Medium withstand voltage | ≥2500VAC | |
| Insulating resistance | ≥100MΩ | |
| Switching time | ≤10mS | |
| Frequency range | 47-63Hz | |
| Operating temperature | -20-70℃ | |
| Load current safety factor | Resistive load 50-60% | |
| Inductive load 30-40% | ||
Compliant with GB national standards, with CCC and CQC certification for domestic sales and bidding compliance.
Comply with CE, RoHS, REACH and EN standards, approved by TÜV & VDE, and support ATEX certification for explosive hazardous areas.
UL, CUL and CSA certified, conforming to North American electrical safety specifications for US and Canada market access.
Adapt to Japanese PSE and Korean KC certification, follow JIS and KS local standards to meet market access regulations of Japan and South Korea.
Custom voltage & current, AC/DC type, zero-cross or random trigger.
Custom mounting, terminals and non-standard dimensions.
Custom heat dissipation, high isolation, potting and anti-corrosion protection.
Overheat/overcurrent protection, anti-interference, delay and soft start optional.
Custom logo, marking, OEM/ODM and personalized solution design.
Regular customization: 3-7 working days
Complex Customization: 7-15 working days
Urgent Sampling: 24-72 hours
2222 US dollars
Conventional products have no minimum order quantity. Customized products can be consulted with customer service
The delivery time usually varies depending on the quantity and model of the order, usually 3-5 days. For specific times, please consult us